First study
One case. One version. Visible limits.
This walkthrough describes the supported route; it does not represent a completed customer installation or engineer-approved result.
Run the exact five-bus sample
The downloadable file is a sanitized derivative of the reviewed synthetic fixture. Only its personal user_name metadata was cleared; electrical values and every other archive member are byte-identical to the source fixture.
Download the native sample Read the public proof record
Verify the sample file SHA-256 before opening: 6741afaabf9ab0190cbec2d05d7cfa6521cfeaa9fe0e6f4d2530fe7e51a978d3. The archive contains five buses, seven lines, two generators and three loads. It is educational material, not an installer or qualified design.
- Open the file in a compatible PowerSystem desktop. Open the downloaded
.veragridin the native project window. Keep the original sample unchanged and use a disposable project copy. - Inspect exact inputs in Plan. Ask the native study tools to run
study_equipmentfor the summary and confirm the returned artifact SHA-256 matches the downloaded file. Review the buses, branches, loads and generators; do not edit or repair values. - Save the immutable case in Build. Use
study_case_managewithoperation="save", labelPublic synthetic base case, and request{"kind":"power-flow","expected_artifact":"<exact discovered SHA-256>"}. Use a fresh request key for submission. - Submit that exact case version. Use
study_case_submitwith the savedcase_idandversion; do not substitute a newer or guessed version. Pollstudy_statusuntil a terminal status. - Read the retained result. Use
study_runsandstudy_resultsfor the returned receipt. Expect a balanced AC base-case run only; no N-1 is implied. Compare nothing unless a second compatible run exists.
The balanced AC base case converged. Bus voltage range: 1.000000–1.010000 pu. Active losses: 0.119856 MW. Independent line-pi nodal balance error: 1.86e-12 MVA (limit 0.0001 MVA). No N-1 study or engineering approval is implied. This result is reproducibility evidence for the synthetic case, not independent validation, an engineering recommendation, or human approval. If no compatible customer package/account is available, the sample cannot be run through an unavailable service.
- Open a copy of your native project. Preserve stable IDs, diagrams, scenarios and original input values. Investigate data warnings rather than asking AI to repair them silently.
- Inspect the exact equipment and units. Confirm load/generator P in MW, Q in MVAr, voltage setpoint in pu and continuous branch rating in MVA. Record source or synthetic assumptions beside the candidate.
- Save a named case and version. Select one snapshot/scenario. Changed inputs produce a new immutable version; a prior receipt is not reused as proof for changed data.
- Choose an admitted profile. Balanced AC power flow examines one exact saved snapshot. Select outages separately if screening is required; power flow never adds N-1 implicitly.
- Submit and wait for the worker. Read status, warnings and the solver/configuration identities. A failed, islanded or unsupported study remains explicit instead of being converted to a zero result.
- Review measured results. Inspect bus voltages, branch flows, losses and any limit violations in the native result view. Compare only compatible cases and independently verify answers within the admitted profile.
- Retain evidence, then decide. Reopen the saved project and receipt. An AI response or completed job does not accept a candidate, approve engineering or Apply to Original.