Native property registrations from the pinned engine; not certification of this equipment. Use native IDs and inspect actual object state. Absence is not zero. Definitions/units/types below are exact source declarations, not guessed conversions. See Projects.
P
Active power
Unit: MW Type: float Profile: P_prof
Pmin
Minimum active power. Used in OPF.
Unit: MW Type: float Profile: Pmin_prof
Pmax
Maximum active power. Used in OPF.
Unit: MW Type: float Profile: Pmax_prof
Q
Reactive power
Unit: MVAr Type: float Profile: Q_prof
Qmin
Minimum reactive power.
Unit: MVAr Type: float Profile: Qmin_prof
Qmax
Maximum reactive power.
Unit: MVAr Type: float Profile: Qmax_prof
control_mode
Generator control mode
Unit: not declared Type: GeneratorControlMode Profile: control_mode_prof
control_bus
Control bus
Unit: not declared Type: DeviceType.BusDevice Profile: none declared
Pf
Power factor (cos(phi)). This is used for non-controlled generators.
Unit: not declared Type: float Profile: Pf_prof
Vset
Set voltage. This is used for controlled generators.
Unit: p.u. Type: float Profile: Vset_prof
k_droop
QV droop constant.
Unit: not declared Type: float Profile: none declared
dead_band
Droop dead band.
Unit: kV Type: float Profile: none declared
Snom
Nominal power.
Unit: MVA Type: float Profile: none declared
use_reactive_power_curve
Use the reactive power capability curve?
Unit: not declared Type: bool Profile: none declared
q_curve
Capability curve data (double click on the generator to edit)
Unit: MVAr Type: SubObjectType.GeneratorQCurve Profile: none declared
R1
Total positive sequence resistance.
Unit: p.u. Type: float Profile: none declared
X1
Total positive sequence reactance.
Unit: p.u. Type: float Profile: none declared
R0
Total zero sequence resistance.
Unit: p.u. Type: float Profile: none declared
X0
Total zero sequence reactance.
Unit: p.u. Type: float Profile: none declared
R2
Total negative sequence resistance.
Unit: p.u. Type: float Profile: none declared
X2
Total negative sequence reactance.
Unit: p.u. Type: float Profile: none declared
Rs
Stator winding resistance (AG).
Unit: p.u. Type: float Profile: none declared
Xs
Stator leakage reactance (AG).
Unit: p.u. Type: float Profile: none declared
Xm
Magnetizing reactance (AG).
Unit: p.u. Type: float Profile: none declared
Rr
Rotor resistance (AG).
Unit: p.u. Type: float Profile: none declared
Xr
Rotor reactance (AG).
Unit: p.u. Type: float Profile: none declared
Cost2
Generation quadratic cost. Used in OPF.
Unit: e/MW²/h Type: float Profile: Cost2_prof
Cost0
Generation constant cost. Used in OPF.
Unit: e/h Type: float Profile: Cost0_prof
startup_cost
Generation start-up cost. Used in OPF.
Unit: e/h Type: float Profile: none declared
shutdown_cost
Generation shut-down cost. Used in OPF.
Unit: e/h Type: float Profile: none declared
min_time_up
Minimum time that the generator has to be on when started. Used in OPF.
Unit: h Type: float Profile: none declared
min_time_down
Minimum time that the generator has to be off when shut down. Used in OPF.
Unit: h Type: float Profile: none declared
ramp_up
Maximum amount of generation increase per hour.
Unit: MW/h Type: float Profile: none declared
ramp_down
Maximum amount of generation decrease per hour.
Unit: MW/h Type: float Profile: none declared
enabled_dispatch
Enabled for dispatch? Used in OPF.
Unit: not declared Type: bool Profile: enabled_dispatch_prof
must_run
P >= Pmin constraint. Used in OPF with unit commitment active.
Unit: not declared Type: bool Profile: must_run_prof
emissions
List of emissions
Unit: t/MWh Type: SubObjectType.Associations Profile: none declared
fuels
List of fuels
Unit: t/MWh Type: SubObjectType.Associations Profile: none declared
srap_enabled
Is the unit available for SRAP participation?
Unit: not declared Type: bool Profile: srap_enabled_prof
tpe
Machine type of the generator.
Unit: not declared Type: GeneratorType Profile: none declared
is_static_generator
Use the static generator short-circuit model.
Unit: not declared Type: bool Profile: none declared