Guide contents

Loadability

Kind

loadability

Interpretation

Declare selected loads, stress direction, generator participation and bounded sampling/stop settings. Verify the baseline first and keep each selected outage's result separate. Demand and generator movements use MW/MVAr while stress multipliers are dimensionless; voltage and thermal limits retain native units. The report retains sampled feasible points and the actual first limiting constraint, nonconvergence or configured stopping cause. Inspect the bottleneck's object ID and underlying evidence, not only a headline multiplier. A sampled limit is not a guaranteed hosting capacity, continuation nose or operational approval. Increasing the bound or changing participation is a new configuration/run, not permission to extrapolate past the last verified point.

Run

Discover settings with study definitions. Select an exact network snapshot and case version; inspect readiness. Submit once using study_submit or the case submission tool, monitor study_status, then inspect study_results. Keep input/configuration/solver identities, warnings and failure states.

Compare and accept

Use equivalent settings/units and exact receipts. Unsupported or incompatible inputs remain explicit. Numerical qualification and human acceptance are separate. See Studies.