Harmonics and frequency investigation

Open Specialist engineering → Harmonics or Frequency sweep. Opening these screens starts neither a calculation nor AI. Setup contains named native-bus selection (including nominal voltage), source declarations and editable schedules. Search by name or voltage; exact native IDs remain authoritative. Unknown or missing facts stay unresolved. Select Build to edit, then explicitly Save and Run.

Harmonics uses declared current injections in the bounded passive positive-sequence network. It is not a nonlinear converter model or certified THD/compliance study. Open frequency investigation copies the exact source/reference/selected buses into a new pending setup. It never overwrites another pending setup or runs it. The uniform sweep range is initialized from supplied harmonic orders; review it.

Results prioritizes retained plots. Select a bus, click a plotted sample or Inspect sample in the local-maxima table. The readout shows the nearest retained frequency and its exact value, never an interpolated ordinate. Missing/singular samples remain gaps. A sampled local maximum is not a precisely identified or classified physical resonance. The ideal reference is declared, not an inferred source impedance; R is constant and X/B scale with frequency in this profile.

Compose plots selects one to four separate quantity panels, visible buses, linear/log display axes and up to four exact retained runs. Applying display settings starts no study. Nonpositive log-magnitude points are hidden only in the plot; raw values remain in tables and evidence. Phase always remains linear. Run compatibility checks include workflow/profile, implementation/dependency versions, fundamental frequency and reference bus. Revisions/scenarios remain visible. Differences use shared exact bus/quantity/frequency identities; absent points remain unavailable and phase differences are wrapped to ±180 degrees. Incompatible curves can be inspected but do not produce numerical deltas.

Save plot view stores presentation metadata against its current revision. A conflicting save keeps pending settings; reopen or save a new copy. Saved frequency plots reopen exact immutable receipts without recomputation. Time-domain recorded plot views keep their existing behavior.

Export evidence uses a new ZIP destination and the existing cancellable native export dialog. It contains the plot configuration, source/revision references, exact full samples and comparison CSV/JSON, not original documents or credentials. Existing destinations are never overwritten. All findings require engineering review; none is manufacturer verification or engineering approval.

Four-panel composition can show driving-point impedance and admittance magnitude and phase. Admittance channels are explicitly derived as the reciprocal of the retained driving-point impedance, not as the diagonal of the native Ybus. Missing or zero impedance has no finite derived admittance. The evidence records this basis.