Sommaire du manuel

Generator

Propriétés déclarées du moteur épinglé, pas une certification. Utilisez les identifiants natifs. Les définitions/unités/types sont conservés dans leur langue source sans conversion supposée. Absent n’est pas zéro. Voir Projets.

P

Active power

Unit: MW Type: float Profile: P_prof

Pmin

Minimum active power. Used in OPF.

Unit: MW Type: float Profile: Pmin_prof

Pmax

Maximum active power. Used in OPF.

Unit: MW Type: float Profile: Pmax_prof

Q

Reactive power

Unit: MVAr Type: float Profile: Q_prof

Qmin

Minimum reactive power.

Unit: MVAr Type: float Profile: Qmin_prof

Qmax

Maximum reactive power.

Unit: MVAr Type: float Profile: Qmax_prof

control_mode

Generator control mode

Unit: not declared Type: GeneratorControlMode Profile: control_mode_prof

control_bus

Control bus

Unit: not declared Type: DeviceType.BusDevice Profile: none declared

Pf

Power factor (cos(phi)). This is used for non-controlled generators.

Unit: not declared Type: float Profile: Pf_prof

Vset

Set voltage. This is used for controlled generators.

Unit: p.u. Type: float Profile: Vset_prof

k_droop

QV droop constant.

Unit: not declared Type: float Profile: none declared

dead_band

Droop dead band.

Unit: kV Type: float Profile: none declared

Snom

Nominal power.

Unit: MVA Type: float Profile: none declared

use_reactive_power_curve

Use the reactive power capability curve?

Unit: not declared Type: bool Profile: none declared

q_curve

Capability curve data (double click on the generator to edit)

Unit: MVAr Type: SubObjectType.GeneratorQCurve Profile: none declared

R1

Total positive sequence resistance.

Unit: p.u. Type: float Profile: none declared

X1

Total positive sequence reactance.

Unit: p.u. Type: float Profile: none declared

R0

Total zero sequence resistance.

Unit: p.u. Type: float Profile: none declared

X0

Total zero sequence reactance.

Unit: p.u. Type: float Profile: none declared

R2

Total negative sequence resistance.

Unit: p.u. Type: float Profile: none declared

X2

Total negative sequence reactance.

Unit: p.u. Type: float Profile: none declared

Rs

Stator winding resistance (AG).

Unit: p.u. Type: float Profile: none declared

Xs

Stator leakage reactance (AG).

Unit: p.u. Type: float Profile: none declared

Xm

Magnetizing reactance (AG).

Unit: p.u. Type: float Profile: none declared

Rr

Rotor resistance (AG).

Unit: p.u. Type: float Profile: none declared

Xr

Rotor reactance (AG).

Unit: p.u. Type: float Profile: none declared

Cost2

Generation quadratic cost. Used in OPF.

Unit: e/MW²/h Type: float Profile: Cost2_prof

Cost0

Generation constant cost. Used in OPF.

Unit: e/h Type: float Profile: Cost0_prof

startup_cost

Generation start-up cost. Used in OPF.

Unit: e/h Type: float Profile: none declared

shutdown_cost

Generation shut-down cost. Used in OPF.

Unit: e/h Type: float Profile: none declared

min_time_up

Minimum time that the generator has to be on when started. Used in OPF.

Unit: h Type: float Profile: none declared

min_time_down

Minimum time that the generator has to be off when shut down. Used in OPF.

Unit: h Type: float Profile: none declared

ramp_up

Maximum amount of generation increase per hour.

Unit: MW/h Type: float Profile: none declared

ramp_down

Maximum amount of generation decrease per hour.

Unit: MW/h Type: float Profile: none declared

enabled_dispatch

Enabled for dispatch? Used in OPF.

Unit: not declared Type: bool Profile: enabled_dispatch_prof

must_run

P >= Pmin constraint. Used in OPF with unit commitment active.

Unit: not declared Type: bool Profile: must_run_prof

emissions

List of emissions

Unit: t/MWh Type: SubObjectType.Associations Profile: none declared

fuels

List of fuels

Unit: t/MWh Type: SubObjectType.Associations Profile: none declared

srap_enabled

Is the unit available for SRAP participation?

Unit: not declared Type: bool Profile: srap_enabled_prof

tpe

Machine type of the generator.

Unit: not declared Type: GeneratorType Profile: none declared

is_static_generator

Use the static generator short-circuit model.

Unit: not declared Type: bool Profile: none declared